Is terrazzo noisy underfoot?
The figures, and where each one comes from
| IIC | What is heard in the room below | |
|---|---|---|
| about 25 | footsteps clearly audible, as if in the same room | |
| about 50 | the minimum most codes require | |
| about 55 | normal walking inaudible; research finds complaints fall sharply here | |
| 60 and above | only extreme impacts perceptible | |
| Term | Standard | Direction |
| IIC, impact insulation | ASTM E989 rated, E492 tested | higher is better |
| STC, airborne sound | ASTM E413 rated, E90 tested | higher is better |
| Ln,w, the European equivalent | ISO 717-2 | ⛔ lower is better |
Why the processes are not interchangeable
The reason terrazzo cannot solve this by itself is stated plainly in the acoustic literature: a concrete floor covered directly with a non-resilient material such as tile or stone has a low IIC because there is no give in the system. Terrazzo is exactly that — a hard, dense, ground surface bonded to a slab — so the rating belongs to what is under and over it, not to the finish. That is why the isolation has to be designed before the terrazzo arrives: a floating screed or resilient layer between the slab and the finish, and a decoupled ceiling below. The sand-cushion terrazzo system is the one terrazzo assembly that arrives with an isolation sheet already in it, which is why a specification that has no acoustic design in it will not acquire one when the terrazzo arrives.
What these figures are, and what they are not
IIC is defined by ASTM E989 and measured to ASTM E492; STC by ASTM E413 and E90; the European equivalent is ISO 717-2. The rating scale and the statement that a hard floor on a slab has a low IIC come from the acoustic engineering literature. ⛔ NO IIC VALUE FOR TERRAZZO IS QUOTED HERE. The figure that circulates for a terrazzo floor is one manufacturer's measured value for one product, which is a product data point and not an industry figure, and ⛔ it is not reproduced. ⛔ The numbers in the first column describe the scale, not a specification for any floor; we have not tested the acoustic performance of a floor we supplied.